Minor storage allows exemption from other sections of AS 1940:2017 if liquids stored are under quantities noted except as required by this section. AS 1940-2017 2.1
Commercial buildings like factories, workshops warehouses and hospitals allows for 5,000 litres of diesel to be stored in a tank at least 1 Metre separation from the building. AS 1940-2017 Table 2.1
Construction sites can store 2,500 litres of petrol or 10,000 litres of diesel in steel self-bunded tanks. AS 1940-2017 Table 2.1
Open land having area greater than 2 hectare and used for agriculture use or a golf course or park allows for liquids to be kept at least 1 Mtr away from any boundary, workshop, dwelling or body of water AS 1940-2017 2.2.5.1(c) but recommendation is to follow the below as a guide.

AS 1940-2017 Table 5.4
AS 1940-2017 Table 5.4

For diesel the width of tank or diameter which ever are greater dimension or at least 3 Metres to boundary fences. AS 1940-2017 Table 5.3 For flammable liquids at least 6 Metres but further distance may be required – As a guide refer to separation distances to buildings for petrol above 7,000 Litres capacity. AS 1940-2017 Table 5.3 and Table 5.4 Poly diesel tanks can be used up to maximum capacity of 10,000 Litres but must have minimum separation distance from buildings or boundary fences of 15 Mtrs. AS 1940-2017 2.2.5.2 (a & e )

Separation distance between horizontal tanks when installed together is a minimum of 600mm between such tanks but increases to at least 1 Meter for vertical tanks. AS 1940-2017 5.7.5 and 5.7.6 Tanks for combustible liquids can be stored inside buildings up to a maximum size of 1000 Litres. See further criteria to be met AS 1940-2017 5.6.3.1 Polyethylene diesel storage tanks must not be used on construction sites. AS 1940-2017 2.2.6 A minimum 3 Metre separation is required from a flammable self-bunded tank to any ignition source including the vehicle being refilled. AS 1940-2017 5.9.2 ( g ) Further regulations governing pumping equipment, dispensing points and ignition sources to storage tanks needs to be followed and can be found in AS 1940:2017
Diesel is a C1 combustible liquid. Kerosene or JetA-1 as commonly used for Aircraft is a flammable liquid class 3 and comes under the Hazchem code regulations. Petrol or (Gasoline - USA terminology) is a flammable liquid class 3
Many varieties of petrol are available such as ULP, PULP and high octane fuels such as Avgas used in aeroplanes or race cars.
Please note – all above for reference only and you must consult with your local authorities and fuel supplier for correct site-specific requirements. All information is given as a guide only and full responsibility and interpretation of applicable standards rests solely with the owner of the tanks or property. Ensure full consultation is done with local building regulations and your insurance provider. Reference must be made to any updates to applicable standards at any time. Equipco do not accept any liability or responsibility arising in any way from omissions or errors contained. E&OE. Acknowledgements - all information is taken from AS 1940-2017 regarding tank sizes and separation distance requirements.

Aviation Tanks from 1000 Ltr Cubes to 55,000 Ltr Bunded Tanks and Airport Bulk Fuel storage Facilities are all part of our portfolio.

Service Truck tanks for every application - we offer unique designed packages to suit your fleet or single vehicle. Underground coal, hard rock.

“Built Tough” Mine-Go self bunded(double wall) steel tank range to meet the relentless demands of the mining industry.

Designed for installation where space saving is critical with compact footprint design. Total security of fuel storage on your site.

All steel construction - designed for the most demanding on-site applications in mining, industry and heavy contracting. Constructed to Australian Standards AS1692 and AS1940.

All steel construction. Single wall tank. Constructed to Australian Standards AS1692- 2006. Made in Australia.

Designed for Power-Gen and contractor use for static storage of diesel fuel.

Pump bay compartment with hose reel & storage area. Tank removable for inspection and maintenance. Inspection hatch, spare wheel, flashing light and fire extinguisher.

The all new Fueline range of tanks by Equipco are the best smart tank available for compact use with integrated forklift base on most models. Size range: 50L - 980L

The ET Series is a premium self bunded ( double wall ) fuel storage solution designed for harsh operating environments with minimal site preparation.

All steel construction. Single wall tank. Constructed to Australian Standards AS1692-2006 and AS1657-2018. Made in Australia.
Are you sure you would like to remove this item from the shopping cart?
This item is a part of the approved quote. Removing it will remove all quote items from the cart.